The short answer
Most analyzers connect to a PLC through a 4-20 mA analog signal, relay contacts for alarms, or a digital link such as Modbus or Ethernet. First confirm that the PLC has a spare input of the right type, then wire, scale and test the signal so the PLC shows the correct value.

Common connection types
| Signal | Best for | Keep in mind |
|---|---|---|
| 4-20 mA | One measurement per wire pair | Simple and dependable. Scaling must match in both devices |
| Relay contact | Alarms and on/off status | Gives no measured value |
| Modbus or Ethernet | Multiple values and diagnostics | The PLC must support the protocol, and it takes more setup |
What to check first
- Is there a spare input card channel, or space to add one?
- Is the instrument powered by the loop or does it have its own supply?
- Can shielded cable be run away from motor and drive wiring?
- Does the HMI need a new display, trend or alarm?
- Does anyone have a current backup of the PLC program?
Test it end to end
Simulate low, middle and high values at the instrument and confirm the same values appear on the HMI. Then check that every alarm works.